1 |
2020-11-27 00:00:00 Comment: Proposed site for P/F of 60 MM I/L tiles. 0%
|
2021-02-25 00:00:00 Comment: The thickness of bedding sand + lean concrete + I/L tiles was checked and found 180 mm
instead of 200 mm which is 20 mm less than required and the thickness of bedding sand +
I/L tiles was checke 30%
|
2022-12-07 00:00:00 Comment: At the time of visit work was is in progress.
It was observed that fine sand is being used below the I/L tile instead of coarse sand. It
needs to be rectified.
The thickness of bedding sand and ba 80%
|
Comment: |