2021-01-20 00:00:00 Comment: Proposed site for P/F of I/L tiles. 0%
|
2021-02-25 00:00:00 Comment: The thickness of bedding sand + lean concrete + I/L tiles were checked at 3 different points and
found as average 150 mm instead of 200 mm which is 50 mm less than required.
Department must en 30%
|
2022-12-07 00:00:00 Comment: At the time of visit work was in progress.
The thickness of bedding sand and base concrete under I/L 80mm tiles was checked at 2
points near Shinda Sofa Repair Shop, the thickness of bedding sand f 70%
|